Product Description:
Easily configured for two-level differential, single-point protection, or alarm operations, and can be set for pump-up (fill) or pump-down (drain) automatic dual-level control. The controller can be set for high - low liquid level control for conductive liquids with three conductivity probes.
Conductive liquid is sensed between each search and ground (standard). The controller is also equipped with a sensitivity adjustment to eliminate false actuations in some liquids or foams and can be adjusted to sense between 1K - 100K Ohms. An accessible view on-board LED on top of the controller indicates the on-off state to output contacts and controller status.
Model # | R2-120 |
---|---|
Type | 1 Form C (SPDT) single pole, double throw |
Mounting | Slots for #8 screws, 2 places |
Input | Input types: Adjustable probe conductivity from 1 - 100K Ohms Input voltage: 120V AC |
Electrical Connectors | Direct wire screw terminals |
Electrical Ratings | 12V AC sensing voltage, 10 amps @ 120V AC (1/5 HP), 10 amps @ 30V DC |
List Price | $264 |